|
 |
| |
|
|
| |
|
|
| Air Conditioning is based on the precise
control of temperature, humidity, air flow and air cleanliness. LG
Split air conditioners regulate these elements around the clock to provide
you with a comfortable, relaxing atmosphere. Day and night, year after year. |
| |
|
|
| |
|
|
| Cooling Mode:
Excess room heat is absorbed by a special liquid, a
refrigerant, sealed within the system.
As the refrigerant in the indoor unit absorbs the room heat, it changes into
a gas and is carried through small, copper tubes to an outdoor unit which
releases the heat into the atmosphere.
The gas is converted into a liquid again and flows back to the indoor unit
where it is fanned over it and out into the room. This cycle is repeated
until the preset temperature is reached. |

Click above to enlarge |
| |
|
|
 |
| |
|
|
| |
|
|
| Heating Mode:
Heat pump units also allow the above cycle to be reversed. A
heat pump extracts "free" heat from the outdoor air, even on the coldest
days when the temperature may fall as low as -10 degrees centigrade, and
transfers the heat indoors.
Heat pump units therefore avoid the need for a boiler and allow you to cool
and heat with the same unit, with savings in costs and energy throughout the
year. |

Click above to enlarge |
| |
|
|
|
|
| |
|
|
| |
|
|
 |
| |
|
|
|

|
The Heat Pump is an
electrically driven unit that will provide both
HEATING and COOLING
from the same equipment.
It does this by transferring unwanted / free heat from one area to another
with a process called the
REVERSE CYCLE.
This transfer can be made between air to water, water to air, water to water
or air to air using the same process.
During the COOLING
(Summer) season the Heat Pump performs the same as any
standard air conditioning system. It absorbs heat into the refrigerant from
the area being cooled and transfers and rejects it outside.
However, during the HEATING (Winter)
season, The Heat Pump activates the REVERSE CYCLE
and absorbs heat from outside and transfers this heat, again via
the refrigerant, to the area requiring heating.
|
| |
|
THIS IS AN EXTREMELY ECONOMICAL AND
EFFICIENT SYSTEM, AS THE AVERAGE COEFFICIENT OF PERFORMANCE (C.O.P.) IS
EQUAL TO 1:3 |
For example:
1 Kilowatt of electrical input would
supply approx., 3 Kilowatt of heating output.
|
|
Compared to a C.O.P. of 1 : 1 for an electric heater.
|
Most people think
that when ambient temperatures drop to near freezing point that insufficient
heat is available. THIS IS NOT THE CASE. An efficient Heat Pump can operate
and produce a viable heating output down to at least - 5 degrees centigrade
. Some systems can operate down to - 15 degrees centigrade.
It should be noted, however that at these temperatures the average C.O.P.
will reduce to approx.,
1 : 2 and that an automatic temperature / timer defrost cycle might be
activated for approx., 10 minutes every 1and a half to 2 hours.
Important
Although the difference in cost between the two systems is minimal, a
COOLING ONLY air conditioner CANNOT be converted to a HEAT PUMP and should
be borne in mind when considering air conditioning.
|
 |